|
BASIC CODE
REQUIREMENTS
ELECTRICAL INFORMATION
One-Family Residential
BOXES
Switch, receptacle, and fixture
boxes shall be of sufficient size to provide free space for all the
conductors according to this table.
#14 Wire 2.0 Cubic inches for each
wire
#12 Wire 2.25 Cubic inches for each wire
#10 Wire 2.5 Cubic inches for each wire
# 8 Wire 3.0 Cubic inches for each wire
Cable clamps and spliced grounding
conductors reduce the number of conductors in the box by one each.
Each receptacle or switch reduces conductors in the box by two each.
All junction boxes shall be so
installed that the wiring contained in them can be accessible
without removing any part of the building.
In walls or ceilings constructed of
wood or other combustible material, outlet boxes and fittings shall
be flush with the finished surface.
Grounding continuity between a
grounded metallic outlet box and the grounding circuit of the
receptacle shall be established by means of a bonding jumper between
the box and the receptacle grounding terminal.
CABLES
Where exposed or concealed cables
are installed through bored holes in studs, joists, or other wood
members, holes shall be bored at the approximate centers or at least
1-1/4 inches from the nearest edge. Where this is not possible, a
steel plate at least 1/16 inch in thickness shall cover the cables
for protection against the driving of nails into them. Cables shall
be fastened to the surface every 4-1/2 feet and within 12 inches of
each box, when secured to that box.
Where romex is used with single
gang non-metallic boxes, the cable should be stapled within 8 inches
of the box.
Raceways and cable assemblies shall
be continuous from outlet box to outlet box. (No open splices)
At least 6 inches of free conductor
shall be left at each outlet and switch point for making of joints
or the connection of fixtures and devices.
All conductors shall be spliced or
joined with approved splicing devices, including the bare grounding
wires.
Cables should not be run in the
hollow spaces used as ducts for cold air returns except for short
straight through runs.
Cables shall either be run through
bored holes in joists or on running boards.
In unfinished basements, it is
permissible to secure cables not smaller than #8 directly to the
lower edges of the joists.
UNDERGROUND INSTALLATIONS
All conductors, whether direct
burial or in a raceway, must be approved for a wet location.
PVC conduit shall be a minimum
depth of 18 inches.
Direct buried cables of a
residential branch circuit rated 20 amps or less shall be 12 inches
deep, when protected by G.F.C.I. protection. All other direct buried
cables to be 24 inches deep.
CIRCUITS
For the small appliance load in
kitchen, dining room and breakfast room, two or more 20-amp circuits
shall be provided for all receptacle outlets in these rooms and such
circuits shall have no other outlets or lighting. At least two
appliance circuits shall serve the kitchen counter with G.F.C.I.
protection required for all counter top receptacles. At least one
20-amp circuit shall be provided for laundry receptacles. For fixed
appliances (disposal-dishwasher), a separate circuit is required and
shall not be counted as part of the appliance circuits required in
kitchens. Bathroom receptacles to be on 20-amp circuit serving only
the bathroom.
LIGHTS AND RECEPTACLES
Receptacle outlets shall be
installed so that no point along the floor line in any wall space is
more than six feet, measured horizontally, from an outlet in that
space, including any wall space two feet in width. In kitchen areas,
a receptacle shall be installed at each counter space wider than 12
inches.
At least one wall receptacle shall
be installed in the bathroom (adjacent to the basin), outdoors, in
attached garages, and in each basement (in addition to the required
laundry outlet).
All 120 volt 15 and 20-amp
receptacles, installed in bathrooms, garages, unfinished basements,
and outdoors shall have ground-fault circuit interrupter protection.
At least one lighting outlet shall
be installed in an attic, underfloor space, utility room, and
basement where these spaces are used for storage, or containing
equipment requiring servicing.
At least one wall switch controlled
lighting outlet shall be installed in every room, hallway, stairway,
attached garage and outdoor entrance. Where lighting outlets are
installed in interior stairways, there shall be a wall switch at
each floor level to control the lighting outlet where the difference
between floor levels is six steps or more. A detached garage or
auxiliary building with wiring requires a disconnecting means
nearest the point of entry.
Fixtures in clothes closets are
restricted to:
- A surface mounted incandescent
fixture must clear the front edge of the storage shelf by a 12
inch horizontal clearance, with a completely enclosed lamp.
- A recessed fixture with a solid
lens or a fluorescent fixture shall maintain a 6 inch horizontal
clearance from the front edge of the storage shelf. The use of
all recessed fixtures is restricted. Check with the Electrical
Inspector before the purchase and installation of such fixtures.
IC rating fixtures only.
SERVICE
Service conductors shall be
installed to allow clearance of service drops to conform to code as
follows:
- A minimum of 12 feet above grade
- Not less than 36 inches from
windows, doors, porches, or fire escapes.
- Consult the local utility for
service locations.
- Existing location may not be
according to code.
The service switch shall be
installed at the first accessible location nearest the point of
entrance of the service wires, not more than 8 feet into dwelling.
Service entrance conductors must be
installed in a raceway system. (That is PVC, EMT, Rigid, etc.).
Service panel must not be in a
closet or bathroom.
A clear working space, 30 inches
wide and 36 inches deep, is required in front of the service panel.
When available on the premises, the
metal underground water pipe shall always be used as the grounding
electrode. The water pipe ground shall be supplemented by two ground
rods and bonded to the service entrance panel.
A bonding jumper shall be installed
around the water meter to assure continuity when the meter is
removed or a non-metallic one is installed.
For the grounding conductor of a
wiring system, the sheet metal strap type ground clamp is not
permitted.
All interior metallic water and gas
piping which may become energized shall be bonded together and made
electrically continuous.
The bonding requirements above are
also required when the service is changed to a larger size and the
grounding conductor does not meet the present code requirements.
PVC support is required within 3
feet of each outlet box, junction box, device box, conduit body, or
other conduit termination. PVC support spacing is 3 feet for conduit
sizes ½, ¾, and 1 inch and 5 feet for 1-1/4, 1-1/2, and 2 inch.
|